Carrier 59SC5 gas furnace error codes

Carrier 59SC5 gas furnace code 31: pressure switch did not close

On this older control one code covers both pressure switches: the collector box switch (LPS) or the housing switch (HPS) did not close, or opened again, so the control could not confirm the venting was working. If the low pressure switch stays open over five minutes the inducer stops for 15 minutes before a retry, and after three failed cycles on the housing switch the furnace locks out for three hours.

Photograph of a plain closed furnace cabinet with a metal duct in a tidy, softly lit basement
On this page
Code
31
Equipment
Carrier 59SC5 gas furnace
Models
59SC5A (59SC5) single-stage multipoise condensing gas furnaces
What to do
Often an owner fix

What code 31 means

Carrier's 59SC5 Single Stage 4-Way Multipoise Condensing Gas Furnace - Installation, Start-up, Operating and Service and Maintenance Instructions (59SC5A-11SI) lists 31 as pressure switch did not close, for the 59SC5A (59SC5) single-stage multipoise condensing gas furnaces. An amber status light on the control board, seen through a small window in the blower door, flashes a two-digit code: the count of short flashes is the first digit and the count of long flashes is the second.

What usually causes it

The manual points to these causes for this code, roughly in the order a technician would rule them out:

  • A restricted vent pipe, or water lying in a sagging vent pipe.
  • A plugged condensate drain.
  • Strong wind blowing against the vent.
  • Pressure tubing that is disconnected or blocked.
  • A vent that is the wrong size, or an air leak between the burner area and the blower compartment.
  • A failed inducer motor, low voltage to the inducer, or a faulty or miswired pressure switch.
  • Low incoming gas pressure, on furnaces fitted with a low gas pressure switch.

What you can safely check

  1. Look at the vent pipes outside. High-efficiency furnaces, boilers and tankless heaters breathe through plastic pipes on an outside wall or the roof. From the ground, check that snow, ice, leaves or a nest are not blocking either opening, and clear what you can reach safely.
  2. Look at the condensate drain. Condensing equipment makes water that drains through a small hose or trap. A kinked hose, a full pump or water pooling under the unit can make it shut down. Straighten a kinked hose and empty a full pump reservoir; leave the trap itself to a technician.
  3. Write the code down before you reset. Many controls forget the code once power is cut. Note it, how often it flashes, and when it happens. A technician can then go straight to the right part.
  4. Reset it once. Turn the unit off at its switch, wait a minute, and turn it back on, or use the reset the manual describes. One reset clears a passing glitch. If the same code comes back, stop resetting and book a technician.

When to call a technician

Call if the code returns after one reset, if you saw or smelled anything unusual, or as soon as a check above points at a part inside the unit. Tell the technician the brand, the model number from the rating label, and that the control showed code 31 (the manual's first suspect is a restricted vent pipe, or water lying in a sagging vent pipe). That saves a diagnostic visit from starting at zero.

Step by step for this kind of problem

The Furnace not working troubleshooter walks through the symptom question by question and ends with a clear next step.

Other Carrier 59SC5 gas furnace codes

The full Carrier 59SC5 gas furnace code table lists every code with its meaning, and explains how to read and clear them.

Sources

  1. Carrier, 59SC5 Single Stage 4-Way Multipoise Condensing Gas Furnace - Installation, Start-up, Operating and Service and Maintenance Instructions (59SC5A-11SI) shareddocs.com
  2. ENERGY STAR, Maintenance Checklist (heating and cooling) energystar.gov