Carrier 59SC5 gas furnace error codes: what each one means
Carrier's manual for the 59SC5A (59SC5) single-stage multipoise condensing gas furnaces lists 13 codes. An amber status light on the control board, seen through a small window in the blower door, flashes a two-digit code: the count of short flashes is the first digit and the count of long flashes is the second.

On this page
- Codes listed
- 13
- Turn off and call a pro
- 4
- Often an owner fix
- 3
How to read the code
You can read the status light without opening the furnace: it shows through a little window in the lower (blower) door. A light that stays on means the control has power and sees nothing wrong. A dark light means the board has no power at all, and a fast flicker that never pauses means the incoming power is wired with reversed polarity.
Any other pattern is a two-digit code built from short and long flashes. Count the short ones for the first digit and the long ones for the second, so one short flash then three long flashes is code 13, and three short then one long is code 31. Watch it more than once before writing it down.
The board remembers the most recent fault even when power is cut, and it drops stored codes by itself after 72 hours. A technician can call the last code back up by briefly opening a limit wire or by using the test terminals on the board, which then runs a short test of the inducer, igniter and blower. Both are done inside the control compartment, so they are not owner tasks.
Code 13 and code 14 lockouts clear themselves after three hours. Code 21 does not reset on its own: the label says to switch the power off, wait five minutes and try again. The flame rollout switch behind code 33 has to be reset by hand, and the manual says the cause (poor combustion air, wrong gas pressure, burner problems or venting) must be fixed first.
Carrier 59SC5 gas furnace code table
Codes with a link have their own page with causes and the checks that fit that code.
| Code | What it means | What to do |
|---|---|---|
| Rapid flash | Reversed power polarity. The status light flickers quickly without stopping when the 115 volt supply is wired backwards, and the furnace will not heat until it is corrected. | Technician repair |
| 11 | No stored fault. Shown during a code recall when no earlier fault is stored. Codes are wiped automatically after 72 hours. | Often an owner fix |
| 12 | Blower run after power returns. A normal status: when power comes back during a call for heat, the blower runs for 90 seconds before the furnace starts a fresh heating cycle. | Often an owner fix |
| 13 | Limit circuit lockout. A high temperature limit or the flame rollout switch stayed open for more than three minutes, so the control locked the burner out. It tries again by itself after three hours. | Turn it off and call a pro |
| 14 | Ignition lockout. On the 59SC5 control, code 14 means only an ignition lockout: the burners failed to light and prove flame after four tries in a row, so the control stopped trying. It starts over by itself after three hours, or when power is cycled. | Technician repair |
| 21 | Gas heating lockout. The control found a problem in the gas valve circuit and shut gas heating down. This lockout does not clear itself: power has to be off for five minutes before it will try again. | Turn it off and call a pro |
| 22 | Flame where none should be. The control sees flame while the gas valve is supposed to be closed. It keeps the inducer fan running until the flame signal goes away. | Turn it off and call a pro |
| 23 | Pressure switch stuck closed. A pressure switch reads closed before the inducer fan has started, when it should be open, so the furnace will not begin a heating cycle. | Technician repair |
| 24 | Blown 24 volt fuse. The 3 amp fuse on the control board has blown, so the low voltage circuit that runs the thermostat and controls is dead. | Technician repair |
| 31 | Pressure switch did not close. On this older control one code covers both pressure switches: the collector box switch (LPS) or the housing switch (HPS) did not close, or opened again, so the control could not confirm the venting was working. If the low pressure switch stays open over five minutes the inducer stops for 15 minutes before a retry, and after three failed cycles on the housing switch the furnace locks out for three hours. | Often an owner fix |
| 33 | Limit or rollout switch open. A high temperature limit or the flame rollout switch is open, so the burner is off. The blower runs at least four minutes to cool the furnace; if the switch is still open after three minutes the code turns into lockout 13. | Turn it off and call a pro |
| 34 | Flame not proven. The control did not sense flame during an ignition try, or lost it before the blower came on. It retries up to three more times and then locks out with code 14. | Technician repair |
| 45 | Control circuit lockout. The 59SC5 control board found an internal fault and locked out; unlike the newer control, this lockout clears itself after one hour. Switching the power off and on clears it; if the code returns, the board is replaced. | Technician repair |
Codes that mean turn it off
These codes come from a flame, gas, venting or overheat safety. Leave the unit off and call a licensed technician rather than resetting it repeatedly:
Code by code
No code showing?
If the unit is not working and shows no code at all, start with the Furnace not working troubleshooter. It covers power, settings and supply problems that stop the control from running at all.
More error code tables
Sources
- Carrier, 59SC5 Single Stage 4-Way Multipoise Condensing Gas Furnace - Installation, Start-up, Operating and Service and Maintenance Instructions (59SC5A-11SI) shareddocs.com
- Noritz, How to troubleshoot a tankless water heater noritz.com
- Carrier, Furnace not turning on (help page) carrier.com
- ENERGY STAR, Maintenance Checklist (heating and cooling) energystar.gov
- U.S. Consumer Product Safety Commission, Carbon Monoxide Information Center cpsc.gov