Navien boiler error codes: what each one means
Navien's manual for the NHB condensing heating boilers: NHB-055, NHB-080, NHB-110, NHB-150 lists 29 codes. The NHB shows a three digit E code on its front display with the error icon lit. Between faults the display cycles the supply water temperature and the heating system pressure.

On this page
- Codes listed
- 29
- Turn off and call a pro
- 5
- Often an owner fix
- 1
How to read the code
The NHB is a heat-only boiler, so its codes are all about the heating loop. Its front display trades off every five seconds between supply water temperature and loop pressure; a fault replaces those with an E code and turns on the error icon.
Navien's table for this boiler says how each code clears instead of giving remedies. An auto reset code goes away by itself once the condition is gone. A manual reset code needs the Reset button on the front panel, a power-on reset code clears when the boiler is switched off and back on, and codes marked as an alarm only warn.
Press Mode three times to reach INFO, then use plus and minus to read supply and return temperatures, outdoor temperature and loop pressure in psi. Press Reset to leave. A power cut does not need a reset: the boiler starts again on its own when power comes back.
The owner schedule for the NHB asks you to glance at the pressure and temperature gauge daily for unusually high pressure, look over the vent pipes monthly for leaks or blockage, and have the air intake filter cleaned every three to four months. A clogged intake filter on this boiler stops it and brings up E110.
Navien boiler code table
Codes with a link have their own page with causes and the checks that fit that code.
| Code | What it means | What to do |
|---|---|---|
| E001 | Heat exchanger over temperature. The NHB heat exchanger ran over its temperature limit and the burner stopped. It can clear by itself, by the Reset button or by cycling power. | Turn it off and call a pro |
| E003 | Boiler did not light. The NHB failed to light its burner on a call for heat. Clear it with the Reset button or by turning power off and on. | Technician repair |
| E004 | Boiler sensed a false flame. The NHB saw a flame signal with the burner off. It clears itself once the signal goes away, but a repeat needs a technician. | Turn it off and call a pro |
| E012 | Boiler flame dropped out. The NHB flame went out during a heating cycle. It needs the Reset button or a power cycle to clear. | Technician repair |
| E016 | Boiler overheat. The NHB heat exchanger overheated and the burner shut down. It stays locked until reset by button or power cycle. | Turn it off and call a pro |
| E030 | Boiler exhaust temperature fault. The NHB flue gas temperature is outside its allowed range. The boiler may clear it on its own, or by reset or power cycle. | Turn it off and call a pro |
| E046 | Overheat sensor fault. The sensor guarding the NHB heat exchanger against overheating is reading abnormally; the code clears itself when it reads normally again. | Turn it off and call a pro |
| E047 | Flue thermostat fault. The NHB exhaust thermostat is not working normally. It can clear on its own, by reset or by power cycle. | Technician repair |
| E060 | Gas and air mixer fault. The NHB dual venturi is not working as expected; the manual lists this as an alarm. | Technician repair |
| E109 | Boiler fan fault. The NHB combustion fan motor is not running properly. Clear it with Reset or a power cycle once the cause is fixed. | Technician repair |
| E110 | Exhaust vent blocked. The NHB decided its exhaust vent is closed off, so flue gas cannot leave and it will not keep heating the house. The boiler stays off until the Reset button is pressed or power is cycled. Should the vent turn out to be damaged or disconnected rather than just blocked, leave the boiler shut down for a technician. | Often an owner fix |
| E205 | Supply sensor fault. The NHB heating supply thermistor reads abnormally; it clears itself when the reading returns to normal. | Technician repair |
| E218 | Return sensor fault. The NHB heating return thermistor reads abnormally; the manual lists it as an alarm. | Technician repair |
| E271 | Temperature difference too large. The gap between supply and return water temperature went past the NHB's limit, flagged as an alarm. | Technician repair |
| E278 | System supply sensor fault. The system supply thermistor, on the main heating piping rather than inside the boiler, is reading abnormally. | Technician repair |
| E279 | System return sensor fault. The system return thermistor on the heating piping is giving an abnormal reading. | Technician repair |
| E291 | Supply and return reversed. The return water came back hotter than the supply, which the NHB treats as a limit. Reset or cycle power to clear it. | Technician repair |
| E302 | Low heating water pressure. Pressure in the NHB heating loop fell too low. This code needs a press of the Reset button once pressure is back. | Technician repair |
| E352 | High heating water pressure. Pressure in the NHB loop climbed too high; the code clears itself when pressure drops. | Technician repair |
| E353 | Loop pressure sensor fault. The NHB water pressure sensor is not reading correctly; it clears itself once the signal recovers. | Technician repair |
| E515 | Board component fault. A part on the NHB circuit board is faulty. It shows as an alarm and may clear by reset or power cycle. | Technician repair |
| E517 | Board DIP switch fault. The DIP switches on the NHB board are set in a way it rejects. Reset or cycle power after correction. | Technician repair |
| E594 | Board memory fault. The EEPROM on the NHB circuit board is faulty, shown as an alarm. | Technician repair |
| E615 | Microcontroller fault. The NHB's main processor (MCU) found a fault; depending on the case it clears itself or needs a reset or power cycle. | Technician repair |
| E736 | Boiler cascade fault. An NHB set up in a cascade with other boilers has lost communication with them. | Technician repair |
| E740 | Outdoor air sensor fault. The NHB's outdoor temperature sensor is reading abnormally; the boiler then heats to its fixed set temperature instead. | Technician repair |
| E777 | External low water cutoff tripped. An external low water cutoff device wired to the NHB has opened; the code clears itself when the device closes again. | Technician repair |
| E782 | Boiler communication fault. Internal communication on the NHB has failed, flagged as an alarm. | Technician repair |
| E784 | Zone controller communication fault. The NHB has lost contact with an external zone controller, flagged as an alarm. | Technician repair |
Codes that mean turn it off
These codes come from a flame, gas, venting or overheat safety. Leave the unit off and call a licensed technician rather than resetting it repeatedly:
Code by code
No code showing?
If the unit is not working and shows no code at all, start with the Furnace not working troubleshooter. It covers power, settings and supply problems that stop the control from running at all.