Goodman two-stage gas furnace error codes
Goodman two-stage gas furnace code E6: weak flame signal
The furnace is lighting and heating, but the flame sensor signal is low. It is an early warning that the furnace may start failing to light.

On this page
- Code
- E6
- Equipment
- Goodman two-stage gas furnace
- Models
- GMVC96, GCVC96, AMVC96 and ACVC96 two-stage variable-speed
- What to do
- Technician repair
What code E6 means
Goodman's Installation Instructions for *CVC96 & *MVC96 Two-Stage Gas Furnace (IOG-2008A) lists E6 as weak flame signal, for the GMVC96, GCVC96, AMVC96 and ACVC96 two-stage variable-speed. A dual seven-segment LED display on the control board shows a two-character code such as E3 or b9. A ComfortNet communicating thermostat also shows a Call for Service icon and a short fault message.
What usually causes it
The manual points to these causes for this code, roughly in the order a technician would rule them out:
- The flame sensor is coated or oxidized.
- The flame sensor sits in the wrong spot in the flame.
- A lazy flame from wrong gas pressure or poor combustion air, such as a blocked or badly sized intake pipe.
What you can safely check
- Look at the vent pipes outside. High-efficiency furnaces, boilers and tankless heaters breathe through plastic pipes on an outside wall or the roof. From the ground, check that snow, ice, leaves or a nest are not blocking either opening, and clear what you can reach safely.
- Write the code down before you reset. Many controls forget the code once power is cut. Note it, how often it flashes, and when it happens. A technician can then go straight to the right part.
- Reset it once. Turn the unit off at its switch, wait a minute, and turn it back on, or use the reset the manual describes. One reset clears a passing glitch. If the same code comes back, stop resetting and book a technician.
When to call a technician
Call if the code returns after one reset, if you saw or smelled anything unusual, or as soon as a check above points at a part inside the unit. Tell the technician the brand, the model number from the rating label, and that the control showed code E6 (the manual's first suspect is the flame sensor is coated or oxidized). That saves a diagnostic visit from starting at zero.
Step by step for this kind of problem
The Furnace not working troubleshooter walks through the symptom question by question and ends with a clear next step.
Related Goodman codes
Other Goodman two-stage gas furnace codes
The full Goodman two-stage gas furnace code table lists every code with its meaning, and explains how to read and clear them.