Carrier gas furnace code 33: main limit circuit open

Code 33.1: a limit or the flame rollout switch has opened and the burner is off. The blower runs at least four minutes; if the switch is still open after three minutes the code becomes lockout 13.

Photograph of a plain closed furnace cabinet with a metal duct in a tidy, softly lit basement
On this page
Code
33
Equipment
Carrier gas furnace
Models
59SC2E single-stage 35-inch condensing gas furnaces
What to do
Turn it off and call a pro

What code 33 means

Carrier's 59SC2E Single-Stage 35-in. Tall 4-Way Multipoise High Efficiency Condensing Gas Furnace - Installation, Start-up, Operating and Service and Maintenance Instructions (59SC2E-03SI) lists 33 as main limit circuit open, for the 59SC2E single-stage 35-inch condensing gas furnaces. A three-digit display on the control board shows codes such as 33.1, and the status light seen through the sight glass in the blower door flashes the first two digits as short and long flashes.

What usually causes it

The manual points to these causes for this code, roughly in the order a technician would rule them out:

  • A dirty air filter or a restricted duct system.
  • A loose blower wheel or a failing blower motor.
  • A faulty switch or a bad connection.
  • Gas input adjusted wrong.
  • A tripped rollout switch from poor combustion air or a venting fault; it needs a manual reset.

What you can safely check

  1. Check the air filter. A clogged filter starves the system of air and can make a furnace overheat and shut itself down. Turn the furnace off, slide the filter out and hold it to the light; replace it if light barely passes through.
  2. Open the vents and clear the return grille. A furnace needs a free path for air: supply registers open in most rooms, and nothing (furniture, rugs, boxes) covering the large return grille. Too little airflow makes the heat exchanger run hot and trips the limit switch.
  3. Look at the vent pipes outside. High-efficiency furnaces, boilers and tankless heaters breathe through plastic pipes on an outside wall or the roof. From the ground, check that snow, ice, leaves or a nest are not blocking either opening, and clear what you can reach safely.
  4. Write the code down before you reset. Many controls forget the code once power is cut. Note it, how often it flashes, and when it happens. A technician can then go straight to the right part.

When to call a technician

Call if the code returns after one reset, if you saw or smelled anything unusual, or as soon as a check above points at a part inside the unit. Tell the technician the brand, the model number from the rating label, and that the control showed code 33 (the manual's first suspect is a dirty air filter or a restricted duct system). That saves a diagnostic visit from starting at zero.

Step by step for this kind of problem

The Furnace not working troubleshooter walks through the symptom question by question and ends with a clear next step.

Other Carrier gas furnace codes

The full Carrier gas furnace code table lists every code with its meaning, and explains how to read and clear them.

Sources

  1. Carrier, 59SC2E Single-Stage 35-in. Tall 4-Way Multipoise High Efficiency Condensing Gas Furnace - Installation, Start-up, Operating and Service and Maintenance Instructions (59SC2E-03SI) shareddocs.com
  2. Carrier, Furnace not turning on (help page) carrier.com
  3. ENERGY STAR, Maintenance Checklist (heating and cooling) energystar.gov
  4. Noritz, How to troubleshoot a tankless water heater noritz.com