Rheem gas furnace code 10: one-hour lockout

The control has stopped gas heat for one hour because of a repeated fault. It shows 10 in turn with the code for the cause; cooling and fan still work during the lockout.

Photograph of a plain closed furnace cabinet with a metal duct in a tidy, softly lit basement
On this page
Code
10
Equipment
Rheem gas furnace
Models
(-)96V and (-)(-)96MDV series two-stage communicating condensing gas furnaces
What to do
Technician repair

What code 10 means

Rheem's Installation Instructions for 4 Position Condensing Two-Stage Communicating Gas Furnaces w/ECM Blower (-)96V Series (92-24161-124-08) lists 10 as one-hour lockout, for the (-)96V and (-)(-)96MDV series two-stage communicating condensing gas furnaces. A two-digit seven-segment display on the furnace control board shows the code. A steady character is a normal mode; a flashing number is a fault, and two faults can take turns on the display.

What usually causes it

The manual points to these causes for this code, roughly in the order a technician would rule them out:

  • Four failed ignition tries in a row (shown with 11).
  • Flame lost five times in one heat call (shown with 13).
  • Water sensed in the condensate collector box more than once (shown with 59).
  • Unexpected flame sensed when the gas valve was off (shown with 14).
  • The blower was judged dead after the main limit stayed open too long (shown with 61).
  • An internal control fault (shown with 93).

What you can safely check

  1. Write the code down before you reset. Many controls forget the code once power is cut. Note it, how often it flashes, and when it happens. A technician can then go straight to the right part.
  2. Check that gas is reaching the house. If other gas appliances (stove, dryer) also do not work, the problem is the gas supply, so call your gas utility. Do not try to light anything or adjust the gas valve yourself.
  3. Look at the condensate drain. Condensing equipment makes water that drains through a small hose or trap. A kinked hose, a full pump or water pooling under the unit can make it shut down. Straighten a kinked hose and empty a full pump reservoir; leave the trap itself to a technician.
  4. Look at the vent pipes outside. High-efficiency furnaces, boilers and tankless heaters breathe through plastic pipes on an outside wall or the roof. From the ground, check that snow, ice, leaves or a nest are not blocking either opening, and clear what you can reach safely.
  5. Reset it once. Turn the unit off at its switch, wait a minute, and turn it back on, or use the reset the manual describes. One reset clears a passing glitch. If the same code comes back, stop resetting and book a technician.

When to call a technician

Call if the code returns after one reset, if you saw or smelled anything unusual, or as soon as a check above points at a part inside the unit. Tell the technician the brand, the model number from the rating label, and that the control showed code 10 (the manual's first suspect is four failed ignition tries in a row (shown with 11)). That saves a diagnostic visit from starting at zero.

Step by step for this kind of problem

The Furnace not working troubleshooter walks through the symptom question by question and ends with a clear next step.

Other Rheem gas furnace codes

The full Rheem gas furnace code table lists every code with its meaning, and explains how to read and clear them.

Sources

  1. Rheem, Installation Instructions for 4 Position Condensing Two-Stage Communicating Gas Furnaces w/ECM Blower (-)96V Series (92-24161-124-08) pts.rheem.com
  2. Noritz, How to troubleshoot a tankless water heater noritz.com
  3. Carrier, Furnace not turning on (help page) carrier.com
  4. U.S. Consumer Product Safety Commission, Carbon Monoxide Information Center cpsc.gov
  5. ENERGY STAR, Maintenance Checklist (heating and cooling) energystar.gov