Lennox ML296 gas furnace error codes: what each one means
Lennox's manual for the ML296DFVK Merit Series downflow two-stage variable speed furnaces lists 40 codes. The seven-segment LED on the 107629-01 ignition control shows a status letter, or an E followed by three digits for a fault. E000 means no fault is stored.

On this page
- Codes listed
- 40
- Turn off and call a pro
- 12
- Often an owner fix
- 6
How to read the code
This Merit furnace uses a non-communicating two-stage, variable speed control, so it works with an ordinary thermostat and its table is shorter than the one for Lennox's communicating furnaces. The display shows a blinking decimal point when idle and letters such as H (gas heat) or C (cooling) while running.
A push button beside the LED opens a menu that changes every five seconds. Releasing it on E lists the ten most recent codes, c erases them after a second press to confirm, and F shows the flame signal in microamps. Flame mode ends after 10 minutes, on a power reset, or when the button is held until three bars appear. These steps are done with the blower door off, which is a technician's job.
The control is set up for a refrigerant leak sensor used with Lennox A2L (low GWP) air conditioners and heat pumps. If it detects a leak, it cuts 24 volt power to the thermostat so no heating or cooling runs, and it runs the blower on high to clear refrigerant from the cabinet and ducts, normally for a seven minute cycle. If a sensor reports a fault instead, the blower runs at a steady airflow until the fault clears. In a furnace only system the sensors must be switched off, or the blower will run all the time.
As on other Lennox furnaces, the Watchguard feature restarts a locked out ignition control after one hour of continuous call for heat. This furnace vents through plastic pipes as a direct vent or non-direct vent unit, which matters for the pressure switch codes.
Lennox ML296 gas furnace code table
Codes with a link have their own page with causes and the checks that fit that code.
| Code | What it means | What to do |
|---|---|---|
| E000 | No stored fault. Shown in the error recall list when there is no code stored in memory. | Often an owner fix |
| A | Continuous fan. A status display: the blower is running in continuous fan mode only. | Often an owner fix |
| H | Gas heating. A status display: gas heat is on, with the stage and airflow after it. It blinks during ignition. | Often an owner fix |
| E110 | Low line voltage. The supply voltage is below the nameplate rating. The alarm clears five seconds after it recovers. | Technician repair |
| E111 | Reversed line polarity. The line voltage wiring is reversed. Operation resumes five seconds after it is corrected. | Technician repair |
| E112 | No ground. No earth ground is detected and the system shuts down until one is provided. | Technician repair |
| E113 | High line voltage. The supply voltage is above the nameplate rating. Operation resumes five seconds after it is back in range. | Technician repair |
| E117 | Poor ground. A warning only that the earth ground is weak. It clears 30 seconds after the ground is fixed. | Technician repair |
| E125 | Control self-check failed. The ignition control found a hardware fault in itself, a critical alert. Cycling power may clear it; a fault that keeps coming back means a new control. | Technician repair |
| E150 | Refrigerant leak detected. The refrigerant sensor reports a leak at or in the indoor coil. The furnace stops heating and cooling and runs the blower on high to clear the refrigerant. The code cannot be cleared while the sensor still reads a leak. | Technician repair |
| E151 | Leak sensor 1 fault. Refrigerant sensor number 1 reports a problem that keeps it from working, and it may need replacing. The blower runs until the fault clears. | Technician repair |
| E152 | Leak sensor 2 fault. The second refrigerant sensor reports a problem that keeps it from working, and it may need replacing. | Technician repair |
| E154 | Leak sensor 1 not communicating. The control lost contact with refrigerant sensor 1, or its sensor DIP switches are set wrong. When contact returns the blower still runs for at least five minutes. | Technician repair |
| E155 | Leak sensor 2 not communicating. The control lost contact with refrigerant sensor 2. After contact returns the blower runs for at least five more minutes. | Technician repair |
| E160 | Wrong type of leak sensor 1. Sensor 1 is not a type approved for this furnace and must be swapped for a Lennox approved part. The blower runs at least five minutes after it clears. | Technician repair |
| E161 | Wrong type of leak sensor 2. Sensor 2 is not a type suitable for this application and must be replaced with an approved part. | Technician repair |
| E163 | Furnace control board failure. The furnace control board has a fault that keeps the furnace from running properly and may need replacing. | Technician repair |
| E164 | Leak sensor test. Shown while the low GWP test button has been pressed. Normal operation returns and the code clears by itself after one minute. | Often an owner fix |
| E200 | Flame rollout lockout. The flame rollout circuit is open or was open, and the furnace is in a hard lockout until the cause is corrected or the switch is replaced. | Turn it off and call a pro |
| E204 | Gas valve miswired. The control sees a wiring problem with the gas valve. It clears once repaired. | Turn it off and call a pro |
| E205 | Gas valve relay shorted. The relay contact that powers the gas valve is shorted. If the wiring is correct the control must be replaced. | Turn it off and call a pro |
| E207 | Igniter circuit open. The hot surface igniter reads open. The furnace resumes once it is repaired. | Technician repair |
| E223 | Low fire pressure switch did not close. On a call for heat the low fire pressure switch did not close, so the burners will not light. | Turn it off and call a pro |
| E224 | Low fire pressure switch stuck closed. The low fire pressure switch stays closed for more than 150 seconds at the start of a call for heat. | Technician repair |
| E225 | High fire pressure switch did not close. The high fire pressure switch did not close when high fire was called for. | Turn it off and call a pro |
| E226 | High fire pressure switch stuck closed. The high fire pressure switch is closed when it should be open. | Technician repair |
| E227 | Pressure switch opened while lighting or running. The low fire pressure switch opened during ignition or while the burners were on, and the gas shut off. | Turn it off and call a pro |
| E229 | Lit on high fire. Information only: the furnace lit on high fire because the low fire switch was slow to close. No action needed. | Often an owner fix |
| E240 | Weak flame signal. The flame signal is low while running. The alert clears when the heating call ends. | Technician repair |
| E241 | Flame present when it should be off. Flame is still sensed when the gas should be off. Gas must be shut off and the valve checked for a leak. | Turn it off and call a pro |
| E250 | Limit switch open. The high limit is open because the furnace ran hot. If it does not close within three minutes the furnace goes into a one hour soft lockout. | Turn it off and call a pro |
| E270 | Ignition lockout. All ignition retries failed with no flame sensed, so the furnace is in a soft lockout until a heat call succeeds. | Technician repair |
| E271 | Lockout after pressure switch retries. Ignition retries ran out and the last one failed when the pressure switch opened. | Turn it off and call a pro |
| E272 | Lockout after pressure switch recycles. The furnace restarted too many times, the last time because the pressure switch opened. | Turn it off and call a pro |
| E273 | Lockout after repeated flame loss. The furnace restarted too many times, the last time because it lost the flame. | Technician repair |
| E274 | Overheat lockout. The limit circuit kept opening, or stayed open over three minutes, so the furnace shut down for one hour. | Turn it off and call a pro |
| E275 | Lockout after out of sequence flame. Flame was sensed out of sequence and has since gone out; the furnace waits in a one hour soft lockout. | Turn it off and call a pro |
| E292 | Blower motor cannot start. The house blower cannot start because of an obstructed wheel or seized bearings. The furnace waits in a one hour soft lockout. | Technician repair |
| E311 | Heat reduced for low airflow. A warning: airflow is restricted, so the furnace trims its firing rate to match, dropping to low fire. | Often an owner fix |
| E390 | Leak sensor relay stuck. The low GWP relay inside the furnace control is stuck. The control board may need replacing. | Technician repair |
Codes that mean turn it off
These codes come from a flame, gas, venting or overheat safety. Leave the unit off and call a licensed technician rather than resetting it repeatedly:
No code showing?
If the unit is not working and shows no code at all, start with the Furnace not working troubleshooter. It covers power, settings and supply problems that stop the control from running at all.
More error code tables
Sources
- Lennox, Installation Instructions ML296DFVK Merit Series Downflow (508521-01, 06/2026) lennox.com
- Noritz, How to troubleshoot a tankless water heater noritz.com
- Carrier, Furnace not turning on (help page) carrier.com
- ENERGY STAR, Maintenance Checklist (heating and cooling) energystar.gov
- U.S. Consumer Product Safety Commission, Carbon Monoxide Information Center cpsc.gov