Lennox gas furnace error codes: what each one means

Lennox's manual for the SL280UHNV and SL280DFNV (SL280V) and EL296DFV two-stage variable speed furnaces lists 73 codes. A single seven-segment LED on the furnace's integrated control board spells out a status letter or an error code one character at a time, so code E250 shows as E, then 2, then 5, then 0.

Photograph of a plain closed furnace cabinet with a metal duct in a tidy, softly lit basement
On this page
Codes listed
73
Turn off and call a pro
15
Often an owner fix
12

How to read the code

The LED sits on the integrated control in the blower compartment, next to a small push button. When nothing is wrong and the furnace is waiting for a call, the decimal point blinks about once a second. During operation it shows a letter for the mode, such as H for gas heat with the stage number (1 or 2) and then the airflow, or C for cooling. Any code that starts with E is a fault or warning.

The control keeps the last ten codes. A technician holds the push button to step through a short menu (a new item every five seconds), lets go on E to read the stored codes, and can pick c to erase them. The same menu has an F mode that shows the flame sensor signal in microamps. The Lennox manual warns that the blower access panel must be in place whenever the burners or blower run, and a switch behind that panel cuts power when it is removed, so leave the menu to a technician.

Most heating faults end in a soft lockout. The built-in Watchguard timer restarts the ignition sequence by itself after one hour of steady call for heat, and five failed tries to light the burners lead to that one hour wait. A limit switch that stays open for more than three minutes also triggers the one hour lockout. A flame rollout trip (E200) is a hard lockout: the sequence chart says it only clears when the thermostat is reset or the power is cycled, and the cause has to be fixed first.

Codes marked as warnings, such as E311 and E312, let the furnace keep running at reduced output or airflow. Codes E400 to E409 come from an optional module that watches a non-communicating outdoor air conditioner or heat pump compressor, so they point at the outdoor unit, not the furnace burner.

Lennox gas furnace code table

Codes with a link have their own page with causes and the checks that fit that code.

Lennox gas furnace codes, from the Installation Instructions SL280UHNV (507649-05, 04/2024)
CodeWhat it meansWhat to do
AAirflow setting. A status display: the control is showing the blower airflow it is aiming for in the current mode.Often an owner fix
CCooling. A status display: the system is cooling, followed by the stage (1 or 2) and the blower airflow.Often an owner fix
dDehumidifying. A status display: the blower is running in dehumidification mode, followed by its airflow.Often an owner fix
hHeat pump heating. A status display: a paired heat pump is heating, followed by the input rate in percent and the airflow.Often an owner fix
HGas heating. A status display: the furnace is burning gas, followed by the stage (1 or 2) and the airflow. It blinks while the burners are lighting.Often an owner fix
dFDefrost. A status display: a paired heat pump is running a defrost cycle.Often an owner fix
UDischarge air temperature. A status display: the control is showing the supply air temperature from an installed discharge air sensor.Often an owner fix
E105Communication problem. On a communicating system, the furnace cannot talk to the thermostat or outdoor unit over its data wires because messages keep failing. It clears once communication returns.Technician repair
E110Low line voltage. The 120 volt supply to the furnace is below the nameplate rating. The alarm clears five seconds after the voltage recovers.Technician repair
E111Reversed line polarity. The hot and neutral wires feeding the furnace are swapped. The furnace returns to normal five seconds after the wiring is corrected.Technician repair
E112No ground. The control cannot find an earth ground, so the system shuts down until a proper ground is restored.Technician repair
E113High line voltage. The 120 volt supply is above the nameplate rating. The furnace resumes five seconds after the voltage is back in range.Technician repair
E114Wrong power frequency. The control does not see normal 60 hertz power. It resumes five seconds after the supply is corrected.Technician repair
E115Low 24 volt power. The 24 volt control circuit has dropped below its 18 to 30 volt range. The control restarts once the voltage recovers.Technician repair
E116High 24 volt power. The 24 volt control circuit is above its normal range. It clears when the control sees correct voltage again.Technician repair
E117Poor ground. A warning only: the earth ground is weak. The furnace keeps working and the warning clears 30 seconds after the ground is fixed.Technician repair
E120Unresponsive device. On a communicating system, a device (usually the outdoor unit) was slow to answer the furnace. It clears when the device responds.Technician repair
E124Thermostat signal lost. The furnace has not heard from its communicating thermostat for more than three minutes. It stops heating and cooling and waits until a valid message from the thermostat arrives again.Often an owner fix
E125Control board self-check failed. The integrated control found a fault in its own hardware during a self-check. It is treated as a critical alert; the control restarts if the fault goes away and clears the code five minutes later.Technician repair
E126Control internal communication. Parts inside the control board are not communicating with each other. Cycling power may clear it; a lasting fault means a new board.Technician repair
E131Settings corrupted. On a communicating system, the control's stored settings are damaged. It keeps running on factory default settings until the system is set up again.Technician repair
E180Outdoor air sensor fault. The outdoor temperature sensor reads shorted or out of range after the control had recognized it. The code clears 30 seconds after the reading recovers.Technician repair
E200Flame rollout lockout. The flame rollout switch, a heat sensor beside the burners that opens if flames spill out of the burner area, is open now or was open earlier. The control shuts the gas off and holds the furnace in a hard lockout.Turn it off and call a pro
E201Blower motor not answering. The control has lost contact with the variable speed blower motor, which can include a power outage. It clears once contact returns.Technician repair
E202Blower motor mismatch. The blower motor size does not match the furnace size the control is set for, so the unit size code needs to be checked.Technician repair
E203Furnace size not programmed. No valid unit size code is stored in the control, a critical alert that is common after a replacement board is fitted.Technician repair
E204Gas valve miswired. The control sees a wiring fault in the gas valve circuit, the valve that lets gas reach the burners. The furnace cannot heat normally until the valve and its wiring are repaired.Turn it off and call a pro
E205Gas valve relay shorted. The relay contact on the control that switches the gas valve is shorted, so the control cannot be sure it can shut the gas valve off. The furnace needs service before it runs again.Turn it off and call a pro
E206Second stage gas relay failed. The relay for high fire has failed, so the furnace finishes the heating call on low fire only. If high fire never works again the control needs replacing.Technician repair
E207Igniter circuit open. The control reads the hot surface igniter, the part that glows to light the gas, as an open circuit. Normal operation resumes once it is fixed.Technician repair
E223Low fire pressure switch did not close. When heat was called for, the low fire pressure switch, which proves the inducer fan is pulling exhaust through the vent, stayed open. The furnace will not light until the switch proves draft.Turn it off and call a pro
E224Low fire pressure switch stuck closed. The low fire pressure switch reads closed for more than 150 seconds at the start of a heat call, before it should. The control will not start a heating cycle while the switch looks stuck.Technician repair
E225High fire pressure switch did not close. On a call for high fire, the high fire pressure switch stayed open, so the control could not confirm strong enough draft for second stage heat. Normal operation returns once the cause is fixed.Turn it off and call a pro
E226High fire pressure switch stuck closed. The high fire pressure switch reads closed when it should be open at the start of a heat call.Technician repair
E227Pressure switch opened while lighting or running. The low fire pressure switch opened during the ignition attempt or while the burners were on, so the control shut the gas off. It lost proof that exhaust was being drawn out.Turn it off and call a pro
E228Inducer calibration failed. The control could not complete its calibration of the combustion air inducer against the pressure switches, which it uses to set the draft. Heating waits until calibration succeeds.Turn it off and call a pro
E229Lit on high fire. Information only: the low fire pressure switch did not close in time, so the control lit the burners on high fire instead. No action is needed. The service literature says this can happen with low supply voltage or very cold outdoor temperatures.Often an owner fix
E240Weak flame signal. While the burners are running, the flame sensor's signal is low. The alert clears after the current heating call ends.Technician repair
E241Flame present when it should be off. The control still senses flame when the gas valve should be closed. The manual says to shut the gas off and check the valve for a leak.Turn it off and call a pro
E250Limit switch open. The primary limit, a heat sensor at the heat exchanger that opens when the furnace runs too hot, is open. The control closes the gas valve and runs the house blower; if the limit has not closed within three minutes, the furnace goes into a one hour soft lockout.Turn it off and call a pro
E252Supply air too hot. During gas heat, the discharge air sensor reads air leaving the furnace that is too hot. It clears when the heating call ends.Turn it off and call a pro
E270Ignition lockout. The furnace used up its tries to light (five trials in all) without the flame sensor seeing a flame, so it is in a soft lockout. Watchguard tries again after one hour, and the code clears after a heating call that finishes normally.Technician repair
E271Lockout after pressure switch retries. The furnace hit its limit of ignition retries and the last one failed because the pressure switch opened, so it is in a soft lockout. It clears after a heating call that finishes normally.Turn it off and call a pro
E272Lockout after pressure switch recycles. The furnace reached its limit of restarts and the last one was caused by a pressure switch opening. It is in a soft lockout until a heating call finishes normally.Turn it off and call a pro
E273Lockout after repeated flame loss. The furnace reached its limit of restarts and the last one was caused by losing the flame. It is in a soft lockout until a heating call finishes normally.Technician repair
E274Overheat lockout. The limit switch opened again and again, or stayed open longer than three minutes, so the control shut the system down into a one hour soft lockout. It is the lockout version of E250.Turn it off and call a pro
E275Lockout after out of sequence flame. Flame was sensed when it should not have been, and that signal has now gone. The furnace waits in a one hour soft lockout.Turn it off and call a pro
E276Calibration lockout. Watchguard pressure switch calibration failed, so the furnace sits in a one hour soft lockout until a calibration succeeds.Turn it off and call a pro
E290Igniter circuit fault. The hot surface igniter, the part that glows red hot to light the gas, or the circuit that powers it has failed. The furnace goes into a one hour soft lockout and clears once a stable flame is proven.Technician repair
E291Heating airflow too low. The blower cannot move the minimum amount of air the furnace needs for heating. The furnace goes into a one hour soft lockout and clears after a heating call finishes normally.Often an owner fix
E292Blower motor cannot start. The house blower motor will not start, for example from a seized bearing or a stuck wheel. The furnace waits in a one hour soft lockout.Technician repair
E294Inducer drawing too much current. The combustion air inducer motor draws more current than it should. The code clears when the current is normal on the next ignition.Technician repair
E295Blower motor overheated. The house blower motor tripped its internal heat protector. The code clears when the blower demand ends.Technician repair
E310Discharge air sensor fault. The supply air temperature sensor reads shorted or out of range.Technician repair
E311Heat reduced for low airflow. A warning only: the blower is in cutback mode because airflow is restricted, so the furnace lowers its firing rate step by step (every 60 seconds) to match the air it can move. Two-stage furnaces drop to low fire.Often an owner fix
E312Low airflow in cooling or fan mode. A warning only: in cooling or continuous fan, the blower is moving less air than its setting because the motor has hit its built-in speed and torque limits. The system keeps running at the reduced airflow.Often an owner fix
E313Indoor and outdoor size mismatch. A warning on communicating systems: the indoor and outdoor capacity codes do not match. The system runs but may fall short on efficiency and capacity.Technician repair
E331Network link (reserved). Listed as a global network communication link problem, but the manual marks it for future use.Technician repair
E334Y1 relay stuck. The first stage cooling relay on the furnace control is stuck on. The control has to be replaced.Technician repair
E347No first stage cooling output. With a non-communicating outdoor unit, the control is not putting out 24 volts on Y1, so first stage cooling has stopped. A critical alert.Technician repair
E348No second stage cooling output. With a non-communicating outdoor unit, the control is not putting out 24 volts on Y2, so second stage cooling has failed. A critical alert.Technician repair
E349R to O link missing. In non-communicating mode, the control sees no 24 volts between R and O, a link needed for heat pump (dual fuel) setups.Technician repair
E370Interlock switch open. The control has lost 24 volts on its DS terminal for two minutes, which it reads as an open interlock switch. It stops all heating and cooling until 24 volts returns for at least 10 seconds or power is reset.Technician repair
E400Compressor overload tripped. The thermostat is calling for cooling but the outdoor compressor is not running because its internal overload has tripped.Technician repair
E401Compressor running too long. The compressor ran more than 18 hours on one thermostat call, or low pressure switch trips were recorded. A critical alert.Technician repair
E402Outdoor pressure trip. The outdoor unit's discharge or suction pressure went out of limits, or the compressor was overloaded.Technician repair
E403Compressor short cycling. The compressor keeps running for less than three minutes per thermostat call.Technician repair
E404Compressor rotor locked. The compressor rotor is locked, so the compressor short cycles.Technician repair
E405Compressor circuit open. The compressor circuit is open, so no current flows to it.Technician repair
E406Compressor start circuit open. Not enough current is passing through the compressor's start circuit sensor.Technician repair
E407Compressor run circuit open. Not enough current is passing through the compressor's run circuit sensor.Technician repair
E408Compressor contactor welded. The compressor contactor has welded shut, so the compressor runs without stopping.Technician repair
E409Compressor low voltage. The 24 volt control voltage at the outdoor unit is under 18 volts; after 10 minutes the compressor is stopped.Technician repair

Codes that mean turn it off

These codes come from a flame, gas, venting or overheat safety. Leave the unit off and call a licensed technician rather than resetting it repeatedly:

Code by code

No code showing?

If the unit is not working and shows no code at all, start with the Furnace not working troubleshooter. It covers power, settings and supply problems that stop the control from running at all.

More error code tables

Sources

  1. Lennox, Installation Instructions SL280UHNV (507649-05, 04/2024) lennox.com
  2. Lennox, Installation Instructions SL280DFNV Dave Lennox Signature Gas Furnace (508150-02) lennox.com
  3. Lennox, Unit Information / Service Literature Corp 1126-L5 (revised 08/2022) lennox.com
  4. Noritz, How to troubleshoot a tankless water heater noritz.com
  5. Carrier, Furnace not turning on (help page) carrier.com
  6. ENERGY STAR, Maintenance Checklist (heating and cooling) energystar.gov
  7. U.S. Consumer Product Safety Commission, Carbon Monoxide Information Center cpsc.gov
  8. Sears Home Services, Water heater problems and troubleshooting searshomeservices.com
  9. U.S. Department of Energy, Energy Saver: Air Conditioner Maintenance (archived June 14, 2026) web.archive.org