Trane S9V2 gas furnace error codes: what each one means

Trane's manual for the S9V2 two-stage condensing gas furnaces with variable-speed inducer lists 24 codes. A seven-segment display on the S9V2 control board shows a status word while the furnace runs, such as Lr1 or ArF, and an error code that starts with E when it finds a problem.

Photograph of a plain closed furnace cabinet with a metal duct in a tidy, softly lit basement
On this page
Codes listed
24
Turn off and call a pro
3
Often an owner fix
11

How to read the code

On the S9V2, the readout on the control board does more than report faults. During heating it can show Lr1 or Lr2, which means the furnace is running a learning routine on that stage, and ArF followed by a number shows the airflow it is delivering (the number times 10). Error codes always start with E, and the list for this model includes codes for the inducer and blower motors, which talk to the board instead of being simply switched on.

The Err menu on this board shows what is wrong right now, and L6F holds the last six faults. A technician clears that history by holding the Option button for five seconds, so note what it says before then. The Cr menu shows the control's code release number, which helps a technician match parts.

Each S9V2 has a personality module, a small plug-in part that carries the settings for that exact model and serial number. The wiring diagram says it must stay in its original furnace. Codes E14 and E15 mean the board cannot read these settings, so swapping boards or modules between furnaces is not a fix.

If your thermostat is single stage, the installer joins W1 and W2 on the board and the readout then shows HT2 the whole time it heats. That is normal for this setup. As on other Trane two-stage boards, the control allows two extra ignition tries and ten restarts, then waits 60 minutes before trying again by itself.

Trane S9V2 gas furnace code table

Codes with a link have their own page with causes and the checks that fit that code.

Trane S9V2 gas furnace codes, from the Product Data - S9V2 Two Stage Condensing Gas Fired Furnace, incl. error code list (22-1938-1D-EN)
CodeWhat it meansWhat to do
Ht1Low-stage gas heat. A status word, not a fault: the burner is running on its lower gas stage.Often an owner fix
Lr1Low-stage learning routine. A status word: the furnace is heating on its lower stage while it runs a learning routine to tune itself.Often an owner fix
HT2High-stage gas heat. A status word: the burner is on its upper gas stage. With a single-stage thermostat the board shows this whenever it heats.Often an owner fix
Lr2High-stage learning routine. A status word: the furnace is running a learning routine on its upper gas stage.Often an owner fix
ArFAirflow readout. Not a fault: the board is showing the blower airflow, as a number to multiply by 10.Often an owner fix
CL1Low-stage cooling. A status word: the blower is serving the air conditioner on its first stage.Often an owner fix
CL2High-stage cooling. A status word: the blower is at the higher airflow for second-stage cooling.Often an owner fix
HP1Heat pump, low stage. A status word: a heat pump outside is heating on its first stage while the furnace blower runs.Often an owner fix
HP2Heat pump, high stage. A status word: the heat pump is heating on its second stage.Often an owner fix
dFtDefrost. A status word: the outdoor heat pump is clearing frost from its coil, a normal winter event.Often an owner fix
E01Internal board failure. The S9V2 control has detected a failure inside itself and cannot run the furnace properly.Technician repair
E04Heat safety switch open. The main limit, a rollout switch or a reverse airflow switch has opened, so the board turns the gas off until it closes.Turn it off and call a pro
E05Unexpected flame. The board senses flame while the gas should be off, a sign of a gas control fault.Turn it off and call a pro
E06Polarity or ground problem. On this board one code covers both power faults: the 120 volt supply is reversed or the furnace ground is poor.Technician repair
E08Low flame current. The flame signal is weak but still enough to keep heating, so the furnace runs while warning of a problem.Technician repair
E09Inducer limit or condensate switch. The inducer limit switch or the condensate switch has opened, and the burner stays off until it closes again.Often an owner fix
E10Inducer not communicating. The S9V2's variable-speed inducer, the fan that pushes exhaust out, did not answer the control board. Without it the furnace cannot prove venting and will not light.Technician repair
E11Gas valve or relay output fault. The board found a gas valve stage, or its backup safety relay, in the wrong state for what it commanded, and it will not run the burner normally.Turn it off and call a pro
E12Fuse open. The fuse on the S9V2 control has blown, so the low voltage side of the furnace has no power.Technician repair
E13Blower ID mismatch. The board flags a problem with the blower motor's identity, its horsepower or maker setting, so it cannot be sure it is driving the right motor.Technician repair
E14Personality module missing. The board cannot find the personality module that holds this furnace's settings, and its own backup copy is also bad.Technician repair
E15Unit data corrupt. The settings file for this furnace is unreadable both in the personality module and in the board's own memory.Technician repair
E17Blower motor not answering. The variable-speed blower motor did not respond when the board tried to talk to it.Technician repair
E18Blower link fault on the board. The board reports a failure in its own side of the communication link with the blower motor.Technician repair

Codes that mean turn it off

These codes come from a flame, gas, venting or overheat safety. Leave the unit off and call a licensed technician rather than resetting it repeatedly:

Code by code

No code showing?

If the unit is not working and shows no code at all, start with the Furnace not working troubleshooter. It covers power, settings and supply problems that stop the control from running at all.