Goodman modulating gas furnace error codes: what each one means

Goodman's manual for the GMVM97 and GCVM97 modulating (ComfortBridge control) lists 14 codes. A row of three seven-segment LEDs on the ComfortBridge control board shows a letter and number code, such as E0 or B9. When the furnace is idle with no fault it shows IdL.

Photograph of a plain closed furnace cabinet with a metal duct in a tidy, softly lit basement
On this page
Codes listed
14
Turn off and call a pro
4
Often an owner fix
2

How to read the code

The display is on the control board inside the furnace. A healthy furnace shows IdL when idle and g1 or gH2 style status codes while heating. Codes starting with E cover ignition, flame, limit and gas valve faults, and codes starting with B cover the variable-speed blower motor.

A furnace that cannot light after three tries in one heating call goes into lockout and shows E0. The control clears the lockout by itself after an hour, or when the 115 volt power is switched off and on, or when the thermostat is turned down for a few seconds and set back. A fault that is still present brings the lockout straight back.

Settings and fault history can also be read through the CoolCloud HVAC phone app, which a technician uses to load the furnace's model data. On power up the furnace spends about a minute calibrating, and the inducer speeds up and slows down during that time; that is normal and not a fault.

This manual lists more codes than the ones on this page. We include only the codes whose meaning and causes the manual spells out in text we could check. If your display shows a code not listed here, note it and give it to your technician.

Goodman modulating gas furnace code table

Codes with a link have their own page with causes and the checks that fit that code.

Goodman modulating gas furnace codes, from the Service Instructions - Modulating Gas Furnaces (RS6612015R8)
CodeWhat it meansWhat to do
E0Ignition lockout. The furnace failed to light after three tries in one call for heat and has locked out. It waits an hour before trying again unless reset.Technician repair
E3Primary limit open. The temperature at the primary limit got high enough to open it during heating, so the burner shuts off while the control protects the heat exchanger.Turn it off and call a pro
E4Flame sensed with no heat call. The control reads a flame signal while the thermostat is not calling for heat, and it will not run a normal cycle.Turn it off and call a pro
E6Low flame signal. After the furnace lights, the flame sensor current is very low, around 1 microamp or less. The furnace warns of it because ignition failures tend to follow.Technician repair
EbGas valve not powered. With a call for heat and the igniter on, the gas valve is not getting the voltage it should, so the burners do not light.Turn it off and call a pro
ECGas valve powered with no heat call. The gas valve has voltage when the thermostat is not calling for heat, so the control stops the furnace.Turn it off and call a pro
B0Blower motor not running. The house blower is not running when the control needs it, and heating stops.Technician repair
B1Blower communication lost. The control board has lost communication with the blower motor, and the furnace will not run.Technician repair
B2Blower horsepower mismatch. The installed blower motor's horsepower does not match the furnace's stored model data, and the furnace will not run.Technician repair
B3Blower in a limiting condition. The blower motor is running in a power, temperature or speed limit and holding back. The furnace keeps going but moves less air than intended.Often an owner fix
B4Blower lost rotor control. The blower motor sensed high current or lost control of its rotor and stopped, so the furnace stops too.Technician repair
B5Blower failed to start. The blower motor failed to start ten times in a row and the furnace has stopped.Technician repair
B6Blower voltage or overheat shutdown. The blower motor shut down because of high or low line voltage or because its power module overheated.Technician repair
B9Low indoor airflow. The blower is delivering less air than the control is calling for, so the furnace runs at reduced output and may hold back from higher firing rates.Often an owner fix

Codes that mean turn it off

These codes come from a flame, gas, venting or overheat safety. Leave the unit off and call a licensed technician rather than resetting it repeatedly:

Code by code

No code showing?

If the unit is not working and shows no code at all, start with the Furnace not working troubleshooter. It covers power, settings and supply problems that stop the control from running at all.

More error code tables

Sources

  1. Goodman, Service Instructions - Modulating Gas Furnaces (RS6612015R8) mobile.goodmanmfg.com
  2. Carrier, Furnace not turning on (help page) carrier.com
  3. U.S. Consumer Product Safety Commission, Carbon Monoxide Information Center cpsc.gov
  4. ENERGY STAR, Maintenance Checklist (heating and cooling) energystar.gov
  5. Noritz, How to troubleshoot a tankless water heater noritz.com