Carrier two-stage gas furnace error codes: what each one means
Carrier's manual for the 58TP0B, 58TP1B two-stage 80% furnaces and 59TP6C two-stage condensing furnaces lists 26 codes. A three-digit display on the control board shows codes like 32.2, and the status light seen through the sight glass on the blower door flashes only the major code as short then long flashes.

On this page
- Codes listed
- 26
- Turn off and call a pro
- 4
- Often an owner fix
- 3
How to read the code
The 58TP0B, 58TP1B and 59TP6C use the same two-stage control and the same code table. Through the sight glass in the blower access door you see only the major code: the short flashes give the first digit and the long flashes the second, so one short and three long flashes is a 13 code.
The display on the board adds a minor digit after a dot, for example 14.2 or 31.7. The minor digit tells a technician which switch, stage or event tripped. In normal running the display shows letters: idL at rest, Ht1 or Ht2 for low or high heat, CL1 or CL2 for low or high cooling.
Up to seven past faults are kept in the FLt menu, even through a power cut, and they clear after 72 hours of powered operation following the last one. Reading them means pressing the door switch in by hand inside the cabinet near live parts, which the manual reserves for service work, so note the flashing code and leave the menu to a technician.
Ignition, flame-loss and limit lockouts reset on their own after three hours. These furnaces have manual-reset limit switches in the gas control area that open on flame rollout or overheating, and the manual says never to bypass them and to correct the problem before they are reset.
Carrier two-stage gas furnace code table
Codes with a link have their own page with causes and the checks that fit that code.
| Code | What it means | What to do |
|---|---|---|
| 10.1 | Reversed power polarity. The status light flashes fast because the 115 volt supply has hot and neutral reversed. The furnace will not run until the wiring is corrected. | Technician repair |
| 12.1 | Heat call at power up. A normal status: the thermostat was calling for heat when power came on, so the blower runs for 90 seconds before heating starts. | Often an owner fix |
| 13.1 | Limit circuit lockout. A limit, draft safeguard, flame rollout or blocked vent switch stayed open longer than three minutes, so gas heat is locked out. The control tries again after three hours. | Turn it off and call a pro |
| 14.1 | Ignition lockout. The furnace could not light the burners and prove flame in four tries, so the control stopped trying. It resets itself after three hours. | Technician repair |
| 14.2 | Flame lost lockout. The burner flame went out three times after the blower had come on during heating, so the control locked out gas heat. It resets itself after three hours. | Technician repair |
| 14.3 | Repeated flame loss lockout. The flame dropped out seven times during one call for heat, so the control locked out gas heat. | Technician repair |
| 14.4 | Low pressure switch lockout. The low-heat pressure switch opened seven times in one call for heat, so the control locked out gas heat. | Technician repair |
| 15.1 | Blower speed lockout. The control detected no speed signal from the blower motor and put the furnace into a lockout, shown as code 15.1. | Technician repair |
| 19.1 | Thermostat communication lost. The furnace lost its link with an InteliSense thermostat. This code only appears once the two have talked at least once, and it points at the thermostat wiring or setup. | Often an owner fix |
| 23.1 | Main pressure switch stuck closed. The main pressure switch reads closed before the inducer has run, so the furnace will not start a heating cycle. The service label lists stuck switches as 23.4 (main) and 23.5 (high-heat). | Technician repair |
| 24.1 | Blown 24 volt fuse. The 3 amp fuse on the control board is blown, so the 24 volt circuit for the thermostat and controls has no power. | Technician repair |
| 31.6 | High-heat pressure switch open. The high-heat pressure switch, or the relay tied to it, did not close when expected or opened again. The manual points to the relay, the gas valve wiring and the 32.2 venting checks. | Technician repair |
| 31.7 | High heat only next cycle. The high-heat pressure switch took longer than 75 seconds to close when moving from low to high heat, so the next cycle runs on high heat only. | Technician repair |
| 32.2 | Low-heat pressure switch open. The low-heat pressure switch failed to close, or dropped out again. After five minutes open the inducer rests for 15 minutes before a retry, and an opening soon after the gas valve comes on forces the next cycle to high heat. | Turn it off and call a pro |
| 33.1 | Main limit circuit open. A limit, draft safeguard, rollout or blocked vent switch has opened and the burner is off. The blower runs at least four minutes, and after three minutes open the code becomes lockout 13. | Turn it off and call a pro |
| 33.2 | Limit trip, high heat only. Listed with the main limit code: the control holds the furnace on high heat for the rest of the current cycle. | Turn it off and call a pro |
| 41.1 | No blower speed at start. The blower motor gave no speed signal when it was told to start. | Technician repair |
| 41.2 | Blower speed signal lost. The speed signal from the blower motor stopped while the motor should have been running. | Technician repair |
| 43.1 | Low-heat switch open, high-heat closed. The control found the low-heat pressure switch open while the high-heat switch was closed, a combination the manual traces to the low-heat switch, its tubing or the gas pressure. | Technician repair |
| 45.1 | Control failure: flame circuit or memory. The board reports a flame circuit fault, a memory mismatch or a sequence error. Cycle power once; if a 45 code returns, the control is replaced. | Technician repair |
| 45.2 | Control failure: gas valve relay. The relay on the board that powers the gas valve will not close, so the burner cannot light. | Technician repair |
| 45.3 | Control failure: memory. The control reports a problem with its EEPROM memory chip. Cycle power once; if a 45 code comes back, the control is replaced. | Technician repair |
| 45.4 | Control failure: communications. The control reports a loss of communications, which the manual groups with the other control failures. Cycle power once and replace the control if it returns. | Technician repair |
| 46.1 | Brief power loss. Power dropped for a moment. Heating stops and picks up again once the supply settles. | Often an owner fix |
| 52.1 | Supply air sensor open. The supply air temperature sensor reads as an open circuit, so the control cannot measure the air leaving the furnace. | Technician repair |
| 52.2 | Supply air sensor shorted. The wires to the supply air temperature sensor read as shorted together. | Technician repair |
Codes that mean turn it off
These codes come from a flame, gas, venting or overheat safety. Leave the unit off and call a licensed technician rather than resetting it repeatedly:
Code by code
No code showing?
If the unit is not working and shows no code at all, start with the Furnace not working troubleshooter. It covers power, settings and supply problems that stop the control from running at all.
More error code tables
Sources
- Carrier, 58TP0B/58TP1B 80% AFUE Two-Stage 4-Way Multipoise Non-Condensing Gas Furnace - Installation, Start-up, Operating and Service and Maintenance Instructions (58TP0B-01SI) shareddocs.com
- Carrier, 59TP6C Two-Stage Non-Communicating Variable 25-Speed ECM Multipoise Condensing Gas Furnace - Installation, Start-up, Operating and Service and Maintenance Instructions (59TP6C-03SI) shareddocs.com
- Noritz, How to troubleshoot a tankless water heater noritz.com
- Carrier, Furnace not turning on (help page) carrier.com
- ENERGY STAR, Maintenance Checklist (heating and cooling) energystar.gov
- U.S. Consumer Product Safety Commission, Carbon Monoxide Information Center cpsc.gov
- Sears Home Services, Water heater problems and troubleshooting searshomeservices.com