Lennox variable capacity gas furnace error codes: what each one means
Lennox's manual for the SLP99DFVK Dave Lennox Signature Collection downflow modulating furnaces lists 64 codes. The seven-segment LED on the modulating 107901-01 control shows a mode letter, two bars for soft disable, or an E with three digits for a fault, one character at a time.

On this page
- Codes listed
- 64
- Turn off and call a pro
- 15
- Often an owner fix
- 7
How to read the code
The SLP99DFVK changes its firing rate in small steps instead of running on fixed stages, so while it heats the display shows h followed by the input rate as a percent of full fire and then the airflow. A blinking decimal point means idle, and two horizontal bars mean soft disable: a communicating thermostat found a device on the bus it does not recognize.
Holding the diagnostic push button cycles a menu every five seconds. On E the control shows its error history; a solid b leaves the list and c clears it, but only if the button is pressed while c is flashing. A solid dash opens Field Test mode, where C starts a pressure switch calibration. These are technician steps done inside the cabinet.
A soft lockout resets itself after one hour if the call for heat is still on, or sooner when the call for heat or the power is cycled. A hard lockout only resets when power to the control is cycled. Code E118 is a hard lockout set when someone manually ended a soft lockout six times within 15 minutes, so repeated resets make things worse, not better. The manual notes that Watchguard ignition lockouts are usually caused by low gas pressure.
Refrigerant leak sensor codes (E150 to E164 and E390) appear in a separate low GWP table for systems with Lennox A2L air conditioners or heat pumps. This furnace is a direct vent unit that takes air in and sends exhaust out through plastic pipes, and the manual's troubleshooting steps start with checking those pipe connections for tightness and blockage.
Lennox variable capacity gas furnace code table
Codes with a link have their own page with causes and the checks that fit that code.
| Code | What it means | What to do |
|---|---|---|
| h | Modulating gas heat. A status display: the furnace is heating, followed by its input rate as a percent and the airflow. | Often an owner fix |
| H | Staged heat. A status display: heat stage 1 or 2 is on, followed by the airflow. | Often an owner fix |
| E105 | Communication problem. Devices on the communicating bus cannot reach each other. | Technician repair |
| E110 | Low line voltage. Supply voltage is below the nameplate rating. | Technician repair |
| E111 | Reversed line polarity. Line voltage polarity is reversed; the furnace resumes five seconds after correction. | Technician repair |
| E112 | No earth ground. No earth ground is found, so the system shuts down until one is provided. | Technician repair |
| E113 | High line voltage. Supply voltage is above the nameplate rating. | Technician repair |
| E114 | Wrong power frequency. The control does not see 60 hertz power. | Technician repair |
| E115 | Low 24 volt power. The 24 volt supply is under its 18 to 30 volt range; the control restarts when it recovers. | Technician repair |
| E117 | Poor ground. A warning that the ground is weak; it clears 30 seconds after it is fixed. | Technician repair |
| E118 | Too many manual resets. A hard lockout: the furnace was taken out of a soft lockout by hand six times within 15 minutes. Only cycling the power clears it. | Technician repair |
| E120 | Unresponsive device. The outdoor unit was slow to answer the indoor unit. | Technician repair |
| E124 | Thermostat signal lost. The communicating thermostat has been silent for more than three minutes. | Often an owner fix |
| E125 | Control self-check failed. The furnace control found a hardware fault in itself, such as the flame sense circuit or shorted pins. | Technician repair |
| E126 | Microcontrollers not communicating. The two microcontrollers inside the board failed to talk to each other. | Technician repair |
| E180 | Outdoor air sensor fault. The outdoor air sensor is shorted or out of range. No error is shown if it is simply disconnected. | Technician repair |
| E200 | Flame rollout lockout. The rollout circuit is open or was open; the furnace is in a hard lockout. | Turn it off and call a pro |
| E201 | Blower motor not answering. The control cannot talk to the blower motor, which can include a power outage. | Technician repair |
| E202 | Blower motor mismatch. The blower motor size does not match the furnace size code. | Technician repair |
| E203 | Furnace size not programmed. No furnace size code is set in the control. | Technician repair |
| E204 | Gas valve miswired. The gas valve circuit is miswired. | Turn it off and call a pro |
| E205 | Gas valve relay shorted. The relay contact switching the gas valve is shorted. | Turn it off and call a pro |
| E207 | Igniter circuit open. The hot surface igniter reads as open. | Technician repair |
| E223 | Low fire pressure switch did not close. The low fire pressure switch stayed open on a call for heat. | Turn it off and call a pro |
| E224 | Low fire pressure switch stuck closed. The low fire pressure switch contacts read closed when they should be open. | Technician repair |
| E225 | High fire pressure switch did not close. The high fire pressure switch did not close on a call for heat. | Turn it off and call a pro |
| E226 | High fire pressure switch stuck closed. The high fire pressure switch contacts read closed when they should be open. | Technician repair |
| E227 | Pressure switch opened while lighting or running. The low fire pressure switch opened during ignition or while running. | Turn it off and call a pro |
| E228 | Pressure switch calibration failed. The control could not complete its pressure switch calibration. It retries after 300 seconds. | Turn it off and call a pro |
| E240 | Weak flame signal. The flame signal is low while the burners run. | Technician repair |
| E241 | Flame present when it should be off. Flame is still sensed out of sequence; shut off the gas and check the valve for leaks. | Turn it off and call a pro |
| E250 | Limit switch open. The limit circuit is open because the furnace ran hot. | Turn it off and call a pro |
| E252 | Supply air too hot. The discharge air temperature is too high during gas heat. | Turn it off and call a pro |
| E270 | Ignition lockout. Ignition retries ran out with no flame sensed; the furnace is in a soft lockout. | Technician repair |
| E271 | Lockout after pressure switch retries. Ignition retries ran out; the last failed when the pressure switch opened. Same checks as E223. | Turn it off and call a pro |
| E272 | Lockout after pressure switch recycles. Too many restarts, the last caused by a pressure switch opening. Same checks as E223 and E225. | Turn it off and call a pro |
| E273 | Lockout after repeated flame loss. Too many restarts, the last caused by flame failure. Same checks as E240. | Technician repair |
| E274 | Overheat lockout. Too many restarts, the last caused by the limit opening or staying open over three minutes. Same checks as E250. | Turn it off and call a pro |
| E275 | Lockout after out of sequence flame. Soft lockout after an E241 out of sequence flame; the flame signal has now gone. | Turn it off and call a pro |
| E276 | Calibration lockout. Soft lockout after too many failed calibration retries. Same checks as E228. | Turn it off and call a pro |
| E290 | Igniter circuit fault. The igniter or the circuit that triggers it has failed. Same checks as E207. | Technician repair |
| E291 | Airflow too low for minimum fire. Airflow is below what the furnace needs even at its lowest firing rate. | Often an owner fix |
| E292 | Blower motor cannot start. The house blower motor cannot start because of seized bearings or a stuck wheel. | Technician repair |
| E294 | Inducer drawing too much current. The combustion air inducer motor's amp draw is too high. | Technician repair |
| E295 | Blower motor overheated. The house blower motor tripped its internal heat protector. | Technician repair |
| E310 | Discharge air sensor fault. The discharge air sensor is shorted or out of range, checked in Field Test mode. | Technician repair |
| E311 | Heat reduced for low airflow. The blower is in cutback because of restricted airflow, so heat output is reduced. | Often an owner fix |
| E312 | Low airflow in cooling or fan mode. In cooling or fan mode the blower is held below its airflow setting by its built-in limits. | Often an owner fix |
| E313 | Indoor and outdoor size mismatch. A warning that the indoor and outdoor capacity codes do not match; operation is not affected. | Technician repair |
| E331 | Network link (reserved). A network communication code reserved for future use. | Technician repair |
| E345 | O relay failed. The relay that drives a heat pump's reversing valve (O terminal) has failed, and the integrated control must be replaced. | Technician repair |
| E347 | No first stage cooling output. No 24 volts from Y1 to C with a non-communicating outdoor unit, so stage 1 cooling failed. | Technician repair |
| E348 | No second stage cooling output. No 24 volts from Y2 to C with a non-communicating outdoor unit, so stage 2 cooling failed. | Technician repair |
| E370 | Interlock switch open. 24 volts has been missing on the DS terminal for two minutes, read as an open interlock; all heating and cooling stop. | Technician repair |
| E150 | Refrigerant leak detected. A refrigerant sensor reports a leak at or in the indoor coil. Heating and cooling stop while the blower clears the refrigerant, and the code stays until the sensor no longer sees a leak. | Technician repair |
| E151 | Leak sensor 1 fault. Refrigerant sensor 1 reports an internal problem and may need replacing. | Technician repair |
| E152 | Leak sensor 2 fault. Refrigerant sensor 2 reports an internal problem and may need replacing. | Technician repair |
| E154 | Leak sensor 1 not communicating. Contact with sensor 1 is lost, or its DIP switches are set wrong; the blower runs at least five minutes after contact returns. | Technician repair |
| E155 | Leak sensor 2 not communicating. Contact with sensor 2 is lost; the blower runs at least five minutes after it returns. | Technician repair |
| E160 | Wrong type of leak sensor 1. Sensor 1 is not suitable for this furnace and must be replaced with a Lennox approved part. | Technician repair |
| E161 | Wrong type of leak sensor 2. Sensor 2 is not suitable for this furnace and must be replaced with an approved part. | Technician repair |
| E163 | Furnace control board failure. The furnace control board has a problem that stops proper operation; it may need replacing. | Technician repair |
| E164 | Leak sensor test. Shown after the low GWP test button is pressed; it clears itself after one minute. | Often an owner fix |
| E390 | Leak sensor relay stuck. A relay on the control that serves the leak sensor system is stuck, which may mean a new indoor control board. | Technician repair |
Codes that mean turn it off
These codes come from a flame, gas, venting or overheat safety. Leave the unit off and call a licensed technician rather than resetting it repeatedly:
No code showing?
If the unit is not working and shows no code at all, start with the Furnace not working troubleshooter. It covers power, settings and supply problems that stop the control from running at all.
More error code tables
Sources
- Lennox, Installation Instructions SLP99DFVK (508589-02) lennox.com
- Noritz, How to troubleshoot a tankless water heater noritz.com
- Carrier, Furnace not turning on (help page) carrier.com
- ENERGY STAR, Maintenance Checklist (heating and cooling) energystar.gov
- U.S. Consumer Product Safety Commission, Carbon Monoxide Information Center cpsc.gov